Products Description
XYCOM XVME-566 Analog Input Module

Technical Specifications
Model:XVME-566
Brand:XYCOM
Product type:VMEbus High Speed Analog Input Module
Power supply:+5V @2.1A VME backplane power
Bus interface:Standard VMEbus,slave communication,support VME interrupt
Form factor:Single-slot 6U VME card
Weight:0.36kg
Resolution:12-bit A/D conversion
Channel configuration:32 single-ended inputs or 16 differential inputs
Throughput:Up to 100kHz aggregate sampling rate
Onboard memory:64KB dual-access RAM for sample storage;256-byte sequence RAM for conversion programming
Programmable gain:Per-channel programmable gain
Input voltage range:0~5V,0~10V,±2.5V,±5V,±10V
Trigger mode:Software trigger,onboard clock trigger,external hardware trigger
VME addressing:A16/D16 compatible,jumper selectable base address
Operating temperature:0℃ ~ +65℃
Storage temperature:-40℃ ~ +85℃
Relative humidity:5%~95%,non-condensing
Certification:CE,UL
System compatibility
XVME-566 belongs to XYCOM XVME series high-speed analog acquisition module.
It installs in XYCOM VME chassis and cooperates with XVME series CPU and I/O modules.
Compatible with turbine,compressor and legacy DCS control systems via VME bus.
Commonly used for power plant,oil & gas,petrochemical old equipment maintenance and spare replacement.
Function
High-speed multi-channel analog signal collection for VME control rack.
12-bit ADC collects pressure,temperature,flow and vibration sensor analog signals.
Support 32 single-ended or 16 differential wiring configuration,differential mode suppress common-mode interference.
64KB 双存取缓存,减轻高速采样下 VME 总线带宽压力,可缓存超过 32000 组采样数据。
256 字节序列内存,可编程自定义通道扫描顺序,每个通道可独立配置增益参数。
Multiple trigger sources for flexible synchronous data acquisition.
After A/D conversion completes,data is stored to onboard RAM and can trigger VME interrupt to notify host CPU.
Transmit buffered sampling data to VME main CPU over VME backplane.
Onboard self-test for ADC circuit,analog front-end,onboard memory,data bus and VME bus interface fault inspection.
Installation
Power off VME chassis.
Insert XVME-566 card into empty single-slot VME position,tighten front panel fixing screw.
Set base address and interrupt level via board jumpers.
Select single-ended or differential channel wiring mode.
Connect sensor analog wiring to front panel 50pin IDC header.
Power on chassis,run hardware self-test.
VME CPU scans bus,identifies the board and starts analog signal acquisition.
Interface
VME P1 backplane connector,front panel 50pin IDC analog input header,LED indicators:PASS,FAULT.
Feature
Single slot 6U VME high speed analog input board,XYCOM XVME series.
Built-in 64KB dual-access RAM buffer,reduce VME bus occupation during high-speed sampling.
Independent per-channel gain configuration and programmable scanning sequence.
Three trigger modes:software,onboard clock,external hardware trigger,suitable for synchronous acquisition tasks.
Differential input design for strong anti-interference in harsh industrial field.
VME slave interface,easy plug-in installation.
Discontinued obsolete VME module,supply only for old production system spare replacement.
Vibration resistant PCB design,suitable for turbine control cabinet.
Diagnostic
FAULT LED on:ADC or analog front-end circuit damage,onboard memory fault,VME bus communication failure;
Cannot be identified by CPU:check VME backplane contact and base address jumper setting;
Reading unstable/jitter:check differential wiring,shield grounding and common-mode noise;
No sampling data:verify channel configuration,trigger setup,input signal amplitude and wiring continuity.
Product Brief
XYCOM XVME-566 is legacy VMEbus 12-bit high-speed analog input module with onboard sample buffer memory.
It provides synchronous high-speed analog signal acquisition for VME control rack,widely used as spare part for turbine and compressor control,petrochemical and power plant old DCS renovation.
Disclaimer
All parameters are for reference only and not for quotation basis. Goods are scarce and will be powered on for inspection before shipment. Overseas delivery lead time 3-7 working days. This item is only used for equipment maintenance and retrofit.