ABB 216DB61 Trip Output & Binary Input Unit

Technical SpecificationsModel: 216DB61Series: ABB REG216 Digital Generator Protection SystemFunction: Combined binary input and trip output unitForm factor: Standard 6U Eurocard fo
Send Inquiry

Products Description
Technical Specifications
  • Model: 216DB61

  • Series: ABB REG216 Digital Generator Protection System

  • Function: Combined binary input and trip output unit

  • Form factor: Standard 6U Eurocard for 19‑inch rack mounting

  • Channels: 16 channels binary input; 8 channels bipolar trip relay outputs

  • Input: Dry contact / DC signal acquisition for breaker status, external interlock and protection status signals

  • Output: Bipolar drive for auxiliary trip relays, executes protection tripping commands

  • Monitoring: Built‑in output amplifier monitoring circuit for trip loop health diagnosis

  • Indicators: Front‑panel LED indicators for each active input and output channel

  • Internal bus: Backplane bus communication with main processing board

  • Operating Temperature: 0℃ ~ +60℃

  • Applicable System: ABB REG216 generator & transformer protection rack

216DB61 is an integrated binary input and trip output board for the ABB REG216 generator protection system. It collects external switch status signals such as circuit breaker position and interlock contacts via 16 binary input channels, transmits status data to the main processor board through backplane bus.
The 8 bipolar trip output channels drive external auxiliary trip relays. When internal protection logic detects generator faults, it executes fast trip commands to disconnect primary equipment. The module features trip‑loop monitoring function to detect abnormal conditions of external trip circuits in advance. LED indicators on front panel provide direct visual status for commissioning and daily maintenance. Standard plug‑in 6U Eurocard design allows convenient on‑site module replacement.
This module is widely deployed in thermal power and hydropower plant generator protection cabinets. Cut off all control power before replacement, confirm hardware revision compatibility. Suitable for on‑site fault replacement and long‑term spare stocking for existing REG216 systems.


Leave Your Message