Bender EDS490-D-2 Locator

Bender ISOSCAN EDS490-D-2 insulation fault locator, 12 channels, AC/DC 70-276V, 2-10mA, RS485 BMS for IT systems spare
Send Inquiry

Products Description


Bender EDS490-D-2 Locator



Core Performance & Industrial Application

The Bender EDS490-D-2 (B91080010) ISOSCAN insulation fault locator automatically pinpoints insulation faults in unearthed AC/DC IT systems without interrupting supply.

It works with an ISOMETER® monitor such as IRDH575 that injects a locating current signal; branch CTs detect the signal and the device identifies the faulty circuit.

It carries 12 measuring channels, each with its own alarm contact, scanned in parallel within 10 s; up to 90 EDS units expand to 1080 channels on one BMS bus.

Adjustable response sensitivity 2-10 mA suits main and control circuits with leakage capacitance.

It provides two common alarm relays (changeover) plus 12 independent channel alarm contacts, graphical LCD, 300-event history memory and RS-485 BMS interface.

It is used as spare replacement in industrial, marine, medical IT and PV DC insulation monitoring systems.


Technical Specifications

▶ Product type: Insulation fault locator (IFLS)

▶ Brand: Bender (ISOSCAN)

▶ Model: EDS490-D-2; order no. B91080010

▶ Supply voltage: AC/DC 70-276 V; AC 42-460 Hz

▶ Response sensitivity: 2-10 mA adjustable (100 Ω/V)

▶ Channels: 12 measuring channels; up to 90 devices / 1080 channels system

▶ Scan time: ≤10 s parallel scan all channels

▶ Alarm outputs: 2 common changeover relays; 12 independent N/O channel contacts

▶ Communication: RS-485 BMS bus, address 1-90

▶ Memory: 300 time-stamped events (FIFO); latching/non-latching selectable

▶ Feature: CT connection monitoring, external test/reset button, graphical LCD

▶ Mounting: DIN rail; internal IP30, terminals IP20

▶ Standard: IEC/EN 61557-9, EN 61326-2-4

▶ Country of origin: Germany

▶ Compliance: CE, UL certification


VV Chen (1).jpg


Industry Applications

Applied in industrial IT systems, shipboard and offshore, medical isolated systems, data centers and PV DC-side insulation fault location spare replacement.


Note: Confirm CT series (W/WR/WS) and supply voltage variant against nameplate before ordering


! This is from our current stock !

ABBNTAC-02 58967441E
ABBNTLS01
ABBNTR002-A
ABBNU8976A
ABBNWX511A-2/R HESG112548R12
ABBO3EC HENF442581R1
ABBO3ED
ABBO3EEB HENF318176R1
ABBO3EGB HENF315118R2
ABBO3EHA HENF315087R2


Leave Your Message


Leave a message