Schneider PJA36100U63AE1 MCCB Circuit Breaker Unit

Schneider PJA36100U63AE1, PowerPacT P frame molded case circuit breaker, 3P 1000A, 600VAC, Micrologic 5.3P trip unit, Modbus communication, used for low voltage main incoming and feeder protection in industrial and commercial power distribution cabinet.
Send Inquiry

Products Description


Schneider PJA36100U63AE1 MCCB Circuit Breaker Unit



Module Feature

PJA36100U63AE1 is Schneider Electric PowerPacT P frame electronic molded case circuit breaker.

It is 3-pole, rated current 1000A, rated voltage 600VAC, equipped with Micrologic 5.3P electronic trip unit, supports long time, short time and instantaneous protection function. Built-in Modbus communication interface, can upload current, voltage, power, energy and fault alarm data to SCADA system. It supports I-Line bus mounting or lug connection, optional accessories include auxiliary switch, alarm switch, shunt trip and undervoltage release. It is widely used as main breaker for factory distribution, data center and building low voltage power cabinet.

Working principle

Current transformer inside the breaker samples three-phase current signal and sends to Micrologic trip unit.

When overload, short time delay or short circuit fault occurs, the trip unit outputs trip command to release mechanism, separate main contacts to cut off fault circuit. The communication module transmits real-time electrical parameters and fault event information to upper monitoring system. Mechanical interlock prevents reclosing after fault trip.

Onboard components

Main contact assembly, arc extinguishing chamber, CT current sensor, Micrologic electronic trip controller, Modbus communication board, operating mechanism, trip release coil, auxiliary and alarm contact set, molded insulated housing.

LED indicators

Front LEDs indicate power supply, communication running, overload pre-alarm and fault trip status. Local display screen shows measured values and fault codes.

Hardware self‑diagnosis

Built-in supervision detects trip unit power loss, communication failure, CT abnormality and internal circuit error. Fault information can be viewed on local display or EcoStruxure Power software.

Programming software

EcoStruxure Power Commission, used for protection parameter setting, Modbus address configuration, fault log reading and trip curve checking.

Electrical & Process Parameters

Model:PJA36100U63AE1 Brand:Schneider Electric Device type:3P electronic molded case circuit breaker Function:Overload, short circuit protection and electrical parameter monitoring for low voltage power distribution loop

Mechanical & Structure

Mounting:I-Line bus or fixed lug mounting inside LV cabinet Protection class:IP20 Housing:Thermoset insulated molded case

Environmental

Operating temperature:-25℃ ~ +70℃ Storage temperature:-40℃ ~ +85℃ Ambient humidity:5~95% non‑condensing

Certification:UL489, CE, IEC

Status:Original Schneider power distribution spare

Installation

Check phase sequence and torque specification during wiring.

Set protection curve parameters according to coordination requirement, test trip and communication function before energizing.

Interface

3-phase main power terminal, auxiliary/alarm dry contact terminal, Modbus communication port, shunt / undervoltage release wiring terminal.

Diagnostic

Overload pre-alarm: Load current exceeds long time setting value, check downstream load condition. Instantaneous trip: Short circuit fault, inspect cable and load equipment. Communication offline: Modbus wiring error, address conflict or trip unit failure.

Product Brief

Schneider PJA36100U63AE1 molded case circuit breaker, PowerPacT P 3P 1000A MCCB spare for industrial low voltage distribution cabinet replacement.


Leave Your Message


Leave a message