Products Description
Allen‑Bradley 1336‑B007‑EAD‑FA2‑L3‑S1 7.5‑HP 460V AC Adjustable Frequency Drive

Technical Specifications
Model:1336‑B007‑EAD‑FA2‑L3‑S1
Brand:Rockwell Allen‑Bradley
Product Type:Complete AC Adjustable Frequency Drive Unit
Applicable Series:1336‑PLUS Constant‑Torque AC Drive
Power Rating:7.5 HP / 5.5 kW
Input:3‑Phase, 380‑480V AC, 50/60 Hz
Output Rated Current:13A
Output KVA:8.6‑10.4KVA
Enclosure Type:EAD (NEMA Type 1 IP20 enclosed cabinet,support direct wall mounting)
Physical Dimension:31.0cm × 22.0cm ×19.0cm
Weight:19.8kg
Factory Options:
‑ FA2: FA2 front‑mount basic control panel,supports local manual operation,parameter viewing and modification
‑ L3: L3 logic interface board,115V AC logic signal level,supports external interlock,enable and fault contact input signals
‑ S1: S1 serial communication option board,RS‑485 SCANport protocol,supports PLC remote control,parameter read‑write and fault‑code upload
Control Mode:Sensorless vector control, V/F control
Speed Regulation Accuracy:Open‑loop ±0.5% rated speed
Overload Rating:150% rated current for 1 minute (constant‑torque)
Operating Temperature:0℃ ~ +40℃
Storage Temperature:-40℃ ~ +70℃
Product Brief:
1336‑B007‑EAD‑FA2‑L3‑S1 is factory‑configured NEMA Type1 IP20 enclosed 7.5‑HP 460V 1336‑PLUS full drive unit,not separate PCB boards. Suffix EAD represents NEMA Type1 IP20 metal enclosed housing,suitable for direct wall‑mount installation without extra user cabinet.
FA2 front basic control panel realizes local manual operation and parameter editing without external HIM hardware.
L3 logic interface board adopts 115V AC signal level,matches legacy production line 115V AC control loops for external enable,interlock and fault signal input.
S1 communication board provides RS‑485 SCANport interface for Allen‑Bradley PLC system,realizes remote start‑stop,speed reference,parameter read‑write and fault information upload.
Internal hardware includes rectifier power stack,IGBT inverter section,main control CPU board,auxiliary power supply and signal sampling‑conditioning circuits.Retains onboard base analog/digital hard‑wired I/O terminals.
Full protections: over‑current,over‑voltage,under‑voltage,over‑temperature,input phase‑loss,motor thermal overload,ground‑fault protection.When performing full‑unit replacement,backup original parameters,check firmware compatibility and run motor auto‑tuning.ESD protection required for installation and commissioning.Separate power and signal cables.
Commonly used for overhaul of legacy fans,pumps,conveyors and process machinery;direct wall‑mount deployment,adapts to equipment with 115V AC interlock control and SCANport network remote operation.