HPE Q1L86A R/T3000 G5 UPS Unit

Q1L86A, HPE R/T3000 G5 rack/tower convertible UPS, 3000 VA / 2700 W, 200/208/240VAC, hot-swap battery, supports extended runtime modules and remote network monitoring for servers and network equipment.
Send Inquiry

Products Description


HPE Q1L86A R/T3000 G5 UPS Unit



Module Feature

Q1L86A is a line-interactive uninterruptible power supply of HPE R/T3000 G5 series.

It supports dual installation modes: 2U rack mount or free-standing tower. It adopts hot-swappable battery design, batteries can be replaced without shutting down the protected load. Optional extended battery modules can greatly prolong backup duration. It is equipped with LCD display for local status viewing, and compatible with optional network management card for remote monitoring and graceful shutdown. Widely stocked as spare for server room, industrial control and network cabinet power protection.

Working principle

Under normal mains supply, the UPS filters and stabilizes AC power for downstream loads while charging internal battery pack.

When mains power fails or voltage is out of tolerance, the inverter converts DC battery power into stable AC output instantly to sustain the load. Built-in management circuit monitors voltage, battery health, load percentage and temperature. It sends alarm notifications and triggers orderly shutdown of servers through management software before battery depletion.

Onboard components

AC voltage regulation circuit, DC-AC inverter module, rechargeable battery pack, LCD control panel, cooling fan, output socket group, optional network management slot and metal chassis.

LED indicators

Front LEDs indicate power on, battery backup active, overload and fault alarm status.

Hardware self‑diagnosis

Automatic self-check for battery health, internal temperature, inverter circuit and load status. Parameters can be viewed locally on LCD or via network management page.

Programming software

HPE Power Protector, used for UPS monitoring, event alert configuration and automatic server shutdown setting.

Electrical & Process Parameters

Model: Q1L86A Brand: HPE Device type: Line interactive UPS Function: Clean power conditioning and backup power supply for servers, switches and network equipment

Mechanical & Structure

Mounting: 2U rack mounting or tower placement Protection class: IP20 Housing: Metal chassis

Environmental

Operating temperature: 0℃ ~ +40℃ Storage temperature: -15℃ ~ +50℃ Ambient humidity: 5~95% non‑condensing

Certification: CE, UL Status: Original HPE power protection spare

Installation

Cut off input power before replacement.

Install in rack or place on flat ground, connect mains input and load power cables, install network card if required, configure shutdown software and test battery backup function after commissioning.

Interface

AC input terminal, multiple AC output sockets, USB port, optional network management port, extended battery port.

Diagnostic

Short backup time: Battery aging or battery not fully charged. Overload alarm: Connected load power exceeds UPS rating. No communication: Network card failure or IP configuration error.

Product Brief

Q1L86A UPS, HPE R/T3000 G5 3000VA/2700W rack/tower UPS spare for server and network equipment emergency power backup replacement.


Leave Your Message


Leave a message